Inspection Status: Approved
Inspection History: ELECTRIC - TEMP POWER FOR TEST
| Date |
Description |
Inspector |
Results |
Comments |
| 12/04/2014 |
ELECTRIC - TEMP POWER FOR TEST |
|
Approved |
IVRS - Inspection :* |
| 12/01/2014 |
ELECTRIC - TEMP POWER FOR TEST |
|
Not ready for Inspection |
PER PLAN SAT E-301 NOTES CALL FOR COPPER WIRING ONLY-NOTE #35 CODE REQUIRES BONDING TYPE FITTINGS ON SUPPLY SIDE NIPPLES (FITTINGS) 250-92 NEC. PROVIDE SIGNED LETTER FROM ENG OF RECORD TO ALLOW THE USE OF AC CONDUCTORS AT SERVICE EQUIP. |