Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - TEMP POWER FOR TEST
Permit Number - T14CM05356
Inspection Description - ELECTRIC - TEMP POWER FOR TEST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/04/2014 | ELECTRIC - TEMP POWER FOR TEST | Approved | IVRS - Inspection :* | |
12/01/2014 | ELECTRIC - TEMP POWER FOR TEST | Not ready for Inspection | PER PLAN SAT E-301 NOTES CALL FOR COPPER WIRING ONLY-NOTE #35 CODE REQUIRES BONDING TYPE FITTINGS ON SUPPLY SIDE NIPPLES (FITTINGS) 250-92 NEC. PROVIDE SIGNED LETTER FROM ENG OF RECORD TO ALLOW THE USE OF AC CONDUCTORS AT SERVICE EQUIP. |