Permit: T14CM05143

Parcel: 113071950

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
12/04/2015 ELECTRIC - SERVICE UPGRADE Approved
07/08/2015 ELECTRIC - SERVICE UPGRADE Partial Approval 1. GAS BOND AND BONDING JUMPER NEEDED AT 2ND STRUCTURE
2. MAIN DISCONNECTING MEANS ARE NEEDED AT 2NND STRUCTURE
3. LABEL ALL BREAKERS
4. NEED ROOF ACCESS
06/03/2015 ELECTRIC - SERVICE UPGRADE Partial Approval 1. LABEL EXTERIOR OF SUB PANELS
2. GROUND CONNECTIONS TO BE PER 250.8 & 250.12
3. A GROUNDING ELECTRODE SYSTTEM IS NEEDED AT 2ND STRUCTURE
4. MAIN DISCONNECTING MEANS ARE NEEDED AT 2ND STRUCTURE
5. PROPERLY IDENTIFY GROUNDED AND GROUNDING CONDUCTORS IN JUNCTION BX
6. SUPPORT RACEWAYS
09/16/2014 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*