Permit: T14CM04984

Parcel: 112071840

Inspection Status: Approved

Inspection History: FIRE - FINAL

Date Description Inspector Results Comments
10/24/2014 FIRE - FINAL Approved
10/13/2014 FIRE - FINAL Denied 1. Fire sprinkler & 5 year check valve inspection pass due - IFC 901.6.1
2. Suite is 140 not 136 - there is a suite 136 already need to change the plans and the permit IFC 505.1
3. Need all fire extinguishers inspected - IFC 901.6.1
4. Need to label the riser room door "RISE ROOM" 3 inch letters
5. Need F.D. key box system installed to access security gates to riser room & suites - IFC 506
6. All security gates shall have a thumb latch type dead bolt lock cannot use double cylinder keyed dead bolt locks. IFC 1008.1.4.4 & 1030.2.1