Inspection History Details
Inspection Status: Partial Approval
Inspection History: FIRE SPKLR - OH PIPING & HYDRO
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/09/2015 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | Passed 200 PSI for 2 hrs. Pending: 2 uprights in concealed space (right side) at entry way need to be added where existing pipe had been removed. Fill in the concealed space with insulation, over the doorway and at the Right of the Entry. Move inspectors test valve if none other found. |