Permit: T14CM04900

Parcel: 205942030

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T14CM04900

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/03/2015 MECHANICAL - FINAL Approved
06/01/2015 MECHANICAL - FINAL Denied 1. SCREW H20 HEATER FLUE SECTIONS TOGETHER - 3 SCREWS EACH
2. CLEAR DRAINAGE BLOCK OPENINGS AND CORRECT PONDING AREA IN FRONT OF BLOCK - S.E. SIDE OF HOUSE
3. REMOVE SOME, NOT ALL, OF FOAM AT CLEANOUT ABS AND PATCH WITH CONCRETE - WEST EXTERIOR
4. INSTALL COVER ON LAUNDRY VENT FAN
5. PROVIDE AT LEAST 8' STEP LADDER FOR ATTIC ACCESS - IF NOT 10'
6. PAINT PVC IRRIGATION RISER