Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/15/2014 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 08/13/2014 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 08/13/2014 | MECHANICAL - INTERMEDIATE | Denied | PROVIDE ACCESS TO ROOF. PROVIDE 1/8 PER FT SLOP ON ALL SECTION OF CONDENSATE DRAIN. TERMINATE CONDESATE WITH AN ELBOW & SHORT RIPPLE TO DIVERT WATER AWAY FROM THE HOUSE. PAINT ALL EXPOSED PVC WITH LATEX PAINT. USE PURPLE PRIMER ON ALL PVC FITTINGS PRIOR TO GLUE. PROVIDE APPROVED SUPPORTS FOR PVC |