Inspection Status: Approved
Inspection History: BUILDING ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 04/17/2015 |
BUILDING ABOVE CEILING |
|
Approved |
IVRS - Inspection :* |
| 04/17/2015 |
BUILDING ABOVE CEILING |
|
Approved |