Permit: T14CM04782

Parcel: 11103092F


Addresses:

3145 E KLEINDALE RD

Inspection Status: Approved

Inspection History: BUILDING ABOVE CEILING

Date Description Inspector Results Comments
04/17/2015 BUILDING ABOVE CEILING Approved IVRS - Inspection :*
04/17/2015 BUILDING ABOVE CEILING Approved PLANS REQUIRE 1" ARMAFLEX. PROVIDE STERILIZATION REPORT. PROVIDE A PROTECTIVE COATING ON EXPOSED ARMAFLEX. PROVIDE TAMPER-PROOF CAPS AT SERVICE PORTS. NO ADHESIVE TAPE ALLOWED EXPOSED ON LINESET. RELOCATE DUCT SMOKE DETECTORS AHEAD OF OUTSIDE AIR