Permit: T14CM04734

Parcel: 133200840

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
11/18/2015 BUILDING - FINAL Approved IVRS - Inspection :*
08/14/2015 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
08/14/2015 BUILDING - FINAL Denied NOT INSTALLED PER PLAN. COMPLETE NOTE CORRECTIONS. SUPPORT. WATER-PROOF. INSTALL AS SHOWN ON PLANS. CLEARANCE ABOVE ROOF, BACKFED BREAKER SHALL BE AT END OF BUS WITH WARNING TAG,. LABEL PANEL. CORRECT PLASTIC BUSHING. REPLACE DAMAGED DISCONNECT CONTACTS (ARCING)