Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
Permit Number - T14CM04694
Inspection Description - ELECTRIC - RECONNECT
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/13/2014 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
08/12/2014 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
08/12/2014 | ELECTRIC - RECONNECT | Denied | BUIT SPLICES NOT CORRECTLY ON GROUND ELECTRODE CONDUCTOR, DID NOT USE PROPER TOOL. A RE-INSPECTION FEE ASSESED USE LICENSED CONTRACTOR | |
08/11/2014 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
08/11/2014 | ELECTRIC - RECONNECT | Denied | SLICES ON GROUND ELECTRODE CONDUCTORS TO BE IRVERESIBLE-CRIMP OR WELD | |
08/08/2014 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
08/08/2014 | ELECTRIC - RECONNECT | Denied | 1.GROUND RODS TO BE FLUSH WITH FINISHED GRADE 2.GROUND WIRE TO BE COMMON TO ALL GROUND RODS,STRAP TO STRUCTURE, SPLICES AT SERVICE TO BE IRREVERSIBLE TYPE- (CRMP OR CADWELD 3.BOND TO GAS & WATER PIPING 4.USE LICENSED OR CONTR TO DO WORK 5.#8 ALUMINUM CONDUCTOR-FUSE AT 40-45AMP MAX |
|
08/07/2014 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
08/07/2014 | ELECTRIC - RECONNECT | Denied | NO COMPLIANCE WITH PREVIOUS INSPECTION WRITE-UP. A RE-INSPECTION FEE ASSESED PA RE-FEE AT 201 N STONE PRIOR TO NEXT INSPECTION-TRIED TO CALL APPLICANT TWICE PER REQUEST NO ANSWER | |
08/04/2014 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
08/04/2014 | ELECTRIC - RECONNECT | Denied | PROVIDE ACCESS INTO BLDG INSTALL A COMPLETE GROUNDING ELECTRODE SYSTEM AS PER 250-NEZ 2-GROUND PODS 6' APART WATER/GAS PIPING BOND SERVICE DISCONNECT NOT RATED FOR OUT DOOR USE NEW FEEDER INTO RATED FOR OUT DOOR MARKER PEN NOT ACCEPTABLE FOR ADDRESS LABEL ON SERVICE USE LICENSED ELECTRICAL CONT TO DO WORK RE-INSPECTION FEE WILL BE ASSESED NEXT INSPECTION FEE WILL BE ASSSESED NEXT INSPECTION IF NO COMPLAINCE |
|
07/30/2014 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
07/30/2014 | ELECTRIC - RECONNECT | Denied | ELECTRICAL SERVICE EQUIP NEEDS UPGRADE - WATER DAMAGE TO EQUIPMENT NOT RATED FOR OUTDOOR USE - NO SERVICE GROUND- OBTAIN PERMIT FOR SERVICE UPGRADE, USE LICENSED CONTRACTOR TO DO WORK PERMANENT ADDRESS LABEL ON SERVICE EQUIP |
|
07/28/2014 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : There is no access to the site.| 920* |
|
07/28/2014 | ELECTRIC - RECONNECT | Denied | disc sw not to code missing ground. bldg locked no msg. provide access into bldg. post address on service resch inspct |