Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T14CM04566
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/26/2015 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
02/20/2015 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
02/20/2015 | ELECTRIC - INTERMEDIATE | Partial Approval | 1. SMOKE ALARMS TO BE MINIMUM 3' FROM SUPPLY REGISTERS 2. PROVIDE MINIMUM R-8 DUCT 3. FRAME REGISTERS MIN 3 SIDES 4. INSULATE HOT WATER LINES 5. BANG PLATES AT GAS, ELEC, & WATER ETC.. 6. PROVIDE PROPER STRAPS AT EXHAUST DUCTS 7. MINIMUM 1" CLEARANCE AT B-VENT 8. PROVIDE COMB AIR WITHIN 12" OF CEILING 9. PROVIDE PLATE ANCHOR AT BACK DOOR 10. GAS PRESSURE TEST OK IN WALLS & CEILING. NO CLEARANCE AT THIS TIME |