Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T14CM04563

Parcel: 117170010


Addresses:

188 E BROADWAY BL


Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T14CM04563

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/24/2014 FIRE - FINAL Approved
10/22/2014 FIRE - FINAL Denied Upon arrival found approx. 30 people in training and cook using the stove with helpers was asked who gave the temp C of O for training the owner stated that building official Armando Quiroz and the health department told her it was okay to train. TFD has not given any approval for a temp C of O.
1. Need hood ansul hood system on the fire alarm (monitoring system) and needs to be tested
2. Correct sprinkler coverage in storage room by kitchen where hot water heater is located 8' 6" off wall not allowed need to be 7' 6" max
3. Plans for egress door on the eastside shows two single doors but now have tri-fold doors they have slide bolt locks not allowed and will need panic hardware.
4. Still need to test emergency lighting and exit signs
10/20/2014 FIRE - FINAL Denied Plans for egress door on the eastside shows two single doors but now have tri-fold doors they have slide bolt locks not allowed and will need panic hardware.
10/17/2014 FIRE - FINAL Not ready for Inspection 1. need fire extinguishers every 75ft of travel.
2. Need panic hardware on emergency exit in the front
3. need kitchen hood final after mechanical final approval.
4. Need a yearly fire alarm and sprinkler report with no deficiencies.
5. Need all tape off heads on final.