Inspection History: FIRE - KITCHEN EXH HOOD FINAL
Permit Number - T14CM04563
Inspection Description - FIRE - KITCHEN EXH HOOD FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/24/2014 | FIRE - KITCHEN EXH HOOD FINAL | Approved | ||
10/20/2014 | FIRE - KITCHEN EXH HOOD FINAL | Denied | 1. Need new plans showing proper placement of all appliances they are set up different from what approved plans show, griddle and 6 burner stove are now each other and both deep fryers are next to the oven. 2. There is also a back shelf 9 ½" X 6' long over the 6 burner stove and griddle. Nozzles have been changed and are correct. 3. Need ansul hooked up to the monitoring system 4. Need a K class fire extinguisher in place within 10 to 20 feet away from hood system. |
|
09/30/2014 | FIRE - KITCHEN EXH HOOD FINAL | Cancelled | IVRS - RI canceled |