Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T14CM04544
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/27/2014 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
07/28/2014 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
07/28/2014 | ELECTRIC - FINAL | Denied | 1. 36" CLEARANCE REQUIRED IN FRONT OF SES 110.26 NEC 2. VERIFY GROUNDING ELECTRODE SYSTEM INTACT 250-NEC 3. BONDING BETWEEN RACEWAY & ENCLOSURE IMPAIRED BY RE WASHERS AND USE OF CHASE NIPPLE, USE CLOSE NIPPLE AND BOND BUSHINGS AT CONDUIT TERMINATIONS TO ENSURE A RELIABLE MECHANICAL CONNECTION AND BOND 250 NEC 4. SUPPORT CONDUITS TO STRUCTURE PER CODE. NOTE:UNITS ENERGIZED PRIOR TO INSPECTORS APPROVAL |