Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/24/2014 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 07/22/2014 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 07/22/2014 | ELECTRIC - SERVICE UPGRADE | Denied | MAINTRAIN FULL SIZE GROUP. GROUND TO TERMINATION COMBING 3 OR 2 CONDUCTORS INTO ONE NOT APPROVED METHOD | |
| 07/21/2014 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 07/21/2014 | ELECTRIC - SERVICE UPGRADE | Denied | 1. INSTALL GROUNDING ELECTRODE SYSTEM- 2 GROUND RODS 6' MIN APART BOND WATER/GAS PIPING 2. GROUND WIRE SPLICE NOT TO CODE IN PANEL 3. INSTALL BOND BUSING FOR 1/2 TERM IN PANEL; RE-WAHERS COMPROMISE BONDING |