Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T14CM04367

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/17/2014 FIRE - FINAL Approved
09/29/2014 FIRE - FINAL Denied 1. Correct upright coverage 130 sq feet coverage in the rear of the building northwest corner head is over 10 feet away from wall. NEED PLAN AND PERMIT FOR ADDING HEADS
2. Also correct upright coverage in suite 120 southeast corner of building front head over 9 fett from wall.
3. Okay to install ceciling tiles in suite 120 but not in the southeast corner of building until inspector sees upright coverage is corrected. NEED PLANS AND PERMIT FOR ADDING SPRINKLER HEADS.
Need to replace out date riser room key in F.D. key box when testing key fail to work, old key was given to contractor on site at time of this inspection.