Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T14CM04367
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/17/2014 | FIRE - FINAL | Approved | ||
09/29/2014 | FIRE - FINAL | Denied | 1. Correct upright coverage 130 sq feet coverage in the rear of the building northwest corner head is over 10 feet away from wall. NEED PLAN AND PERMIT FOR ADDING HEADS 2. Also correct upright coverage in suite 120 southeast corner of building front head over 9 fett from wall. 3. Okay to install ceciling tiles in suite 120 but not in the southeast corner of building until inspector sees upright coverage is corrected. NEED PLANS AND PERMIT FOR ADDING SPRINKLER HEADS. Need to replace out date riser room key in F.D. key box when testing key fail to work, old key was given to contractor on site at time of this inspection. |