Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Permit Number - T14CM04367

Inspection Description - FIRE SPKLR - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/17/2014 FIRE SPKLR - FINAL Approved
10/03/2014 FIRE SPKLR - FINAL Denied 1. Still NEED PLANS AND PERMITS FOR ADDING HEADS.
2. Also need to go over notes given on 9/29/14.
09/29/2014 FIRE SPKLR - FINAL Denied 1. Correct upright coverage 130 sq feet coverage in the rear of the building northwest corner head is over 10 feet away from wall. NEED PLAN AND PERMIT FOR ADDING HEADS
2. Also correct upright coverage in suite 120 southeast corner of building front head over 9 fett from wall.
3. Okay to install ceciling tiles in suite 120 but not in the southeast corner of building until inspector sees upright coverage is corrected. NEED PLANS AND PERMIT FOR ADDING SPRINKLER HEADS.
Need to replace out date riser room key in F.D. key box when testing key fail to work, old key was given to contractor on site at time of this inspection.