Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T14CM04352
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/12/2015 | FIRE - FINAL | Approved | ||
01/05/2015 | FIRE - FINAL | Denied | Duct smoke failed in a/c unit number 1-178 Need lock out on breaker to booster panel Missing one head over sink in the sushi area Check make sure tape removed on upright sprinkler head by bathrooms Need to post Occ. load sign (85) |
|
12/01/2014 | FIRE - FINAL | Denied | 1. This permit has a suite number as 175 problem is 175 is being used already by Goodness juice bar will need to change the suite number for all plans such as sprinkler, alarm, commercial hood system etc. before any final will be given. 2. Need alarm final completed 3. Need to remove tape from sprinkler heads on dining room floor area, need to remove protection plates in restrooms. 4. Post Occ. load sign by main entrance OCC LOAD 85 |