Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T14CM04220
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/21/2015 | FIRE - FINAL | Approved | ||
05/20/2015 | FIRE - FINAL | Partial Approval | 1. Need keys in the F.D. key box 2. Need to check out sound system with the alarm activated need to make sure fire can be heard with sound system on. |
|
05/19/2015 | FIRE - FINAL | Denied | 1. When testing the backup lighting the following failed : a. Rear exit door (outside) from kitchen b. By main electrical panel 2x2 light c. Rear kitchen exit door 2x2 light d. Outside over front main entrance failed 2. Need occupant load sign posted by main entrance door inside (209) and in the patio (41) per approved plans. 3. Per approved plans A8.0 #5 shows the gate from the patio has panic hardware installed 4. Need to check out sound system with the alarm activated need to make sure fire can be heard with sound system on. |
|
05/18/2015 | FIRE - FINAL | Denied | NOT READY |