Inspection History: FIRE - FINAL

Permit Number - T14CM04220

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/21/2015 FIRE - FINAL Approved
05/20/2015 FIRE - FINAL Partial Approval 1. Need keys in the F.D. key box
2. Need to check out sound system with the alarm activated need to make sure fire can be heard with sound system on.
05/19/2015 FIRE - FINAL Denied 1. When testing the backup lighting the following failed :
a. Rear exit door (outside) from kitchen
b. By main electrical panel 2x2 light
c. Rear kitchen exit door 2x2 light
d. Outside over front main entrance failed
2. Need occupant load sign posted by main entrance door inside (209) and in the patio (41) per approved plans.
3. Per approved plans A8.0 #5 shows the gate from the patio has panic hardware installed
4. Need to check out sound system with the alarm activated need to make sure fire can be heard with sound system on.
05/18/2015 FIRE - FINAL Denied NOT READY