Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/12/2015 | FIRE - FINAL | Approved | ||
| 03/09/2015 | FIRE - FINAL | Partial Approval | Temp C of O okay to get final the following needs to get completed: 1. Fire extinguishers needed. 2. FDC sign needed on fence next to FDC connection. 3. Sprinklers needed underneath 2nd story overhang on 2 of 4 buildings. 4. Need to test smoke detectors 5. Apt #15 painted head in hallway 6. Apt #14 painted heads back bedroom and closet 7. Apt #13 taped heads in water heater room and closet 8. Apt #12 Taped head in closet 9. Apt # 6 painted head in closet 10. Apt # 5 Painted head in closet 11. Need spare sprinkler head box 12. Lock out on breaker for fire sprinkler bell |
|
| 02/20/2015 | FIRE - FINAL | Denied |