Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
Permit Number - T14CM04171
Inspection Description - FIRE SPKLR - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/12/2015 | FIRE SPKLR - FINAL | Approved | ||
03/09/2015 | FIRE SPKLR - FINAL | Partial Approval | Painted or taped sprinkler heads in the following areas: 1. Apt #15 painted head in hallway 2. Apt #14 painted heads back bedroom and closet 3. Apt #13 taped heads in water heater room and closet 4. Apt #12 Taped head in closet 5. Apt # 6 painted head in closet 6. Apt # 5 Painted head in closet 7. Need spare sprinkler head box 8. Need lock out on breaker for fire sprinkler bell |
|
02/20/2015 | FIRE SPKLR - FINAL | Denied | 1. Need to add sprinklers underneath 2nd story overhang on 2 of 4 buildings. |