Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
Permit Number - T14CM04142
Inspection Description - PLUMBING - ROUGH, SOIL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/22/2015 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection :* | |
01/16/2015 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
01/16/2015 | PLUMBING - ROUGH, SOIL | Denied | PROVIDE ENGINEERING FOR ALTERATIONS TO INTERCEPTOR OR REPLACE DAMAGED INTERCEPTOR. A WATER TEST IS REQUIRED. CONNECT GREASE FIXTURES TO INLET CONNECTION. CONN OUTLET PIPING TO A 3" OR LARGER DRAIN AS SHOWN. NO PIPING MAY BE DIRECTLY EMBEDDED IN CONCRETE. EXPOSED PIPING SHALL BE CAST IRON OR GALV. PROVIDE CITY APPROVED PLANS | |
07/24/2014 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
07/24/2014 | PLUMBING - ROUGH, SOIL | Denied | REMOVE FLOW CONTROL FITTING CORRECT PIPE SISING PROVIDE MATERIALS APPROVED FOR EXTRIOR , ABOVE GRADE LOCATION PROVIDE DRAINAGE FITTINGS CONNECT ALL GREASE WASTE TO UP STREAM CONNECTION TO INTERCEPTOR REPAIR INTERCEPTOR OT PROVIDE SCREENING CAST IRON MAY NOT DIRECTLY SUMBEDDED IN CONCRETE |