Permit: T14CM04053

Parcel: 125074600


Addresses:

2725 E 8TH ST

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
07/30/2014 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
07/25/2014 EXT METAL CLIPS/EXT SHEATHING Denied 1. STIFFBACK BRACING NOT INSTALLED PER PLAN.
2. COIL STRAP WEST END OF GABLE TRUSSES DOWN TO CORNER KING STUDS.
3. HOLD DOWNS MUST BE NAILED TO KING STUDS ONLY, AND OSB NAILED TO THOSE KINGS ALL THE WAY TO THE TOP PLATE.
4. MISSING MOST H2.5 CLIPS AT TRUSS CONNECTIONS.
5. FINISH OSB INSTALL.
6. ADD RED HEADS WITHIN 12" OF END OF BOTTOM PLATES WHERE NEEDED.