Permit: T14CM04029

Parcel: 117066770


Addresses:

450 E CODD ST


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T14CM04029

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/14/2014 ELECTRIC - FINAL Approved
08/12/2014 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
08/08/2014 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
08/08/2014 ELECTRIC - FINAL Denied 1.REMOVE WIRING AT BACK OF PV DISC.SW AND PLUG HOLE
2. PENETRATION AT TOP OF SERVICE PANEL NOT APPROVED-SEE LISTING NOTES ON PANEL WOOR
3.MIN SIZE GEC FROM MICRO INVESTERS TO SERVICE #8CU PER 690/250NEC
4. HOW WERE CONDUCTORS RUN THRU CARPORT,BE ADVICED,PER 690 NEC NO PU CIRCUITS TO BE RUN WITHIN 10" OF ROOF DECK