Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/14/2014 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 07/14/2014 | ELECTRIC - FINAL | Partial Approval | 1. DOUBLE LUGGED CIRCUITS 2. MISSING BUSHING HOMERUA PENETRATION 3. SEAL OPENING DEAD FRONT 4. GFC PROTECT EXT OUTLETS |
|
| 07/11/2014 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 07/11/2014 | ELECTRIC - FINAL | Partial Approval | 1. ITEM 2&3 STILL NEED CORRECTION, ALL OTHERS OK | |
| 06/27/2014 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 06/27/2014 | ELECTRIC - FINAL | Denied | LEFT MSG AT 8:15 AM 1. PROTECT EXPOSED WIRING @ NORTH EXITDOOR FROM PHYSICAL DAMAGE 2. HAZARDOUS WIRING AT REAR EXTERIOR 4-GAUGE BX GFI PROTECT OUTLETS AND SEAL FROM ELEMENTS WEATHERED COVER 3. PROVIDE ACCESS TO MAIN PANEL & SUBPANEL EXTERIOR 4. OBTAIN SERVICES OF LICENSED ELECTRICAL CONTRACTOR FOR REPAIRS 5. PROVIDE ACCESS TO INTERIOR 6. SEAL OPENINGS INT BOXES 7. MIXED BREAKERS SUBPANEL B 8. BUSHING AT SUB PANEL |