Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - MEDICAL GAS/TEST
Permit Number - T14CM03970
Inspection Description - PLUMBING - MEDICAL GAS/TEST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/15/2015 | PLUMBING - MEDICAL GAS/TEST | Approved | IVRS - Inspection :* | |
02/25/2015 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* | |
02/25/2015 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | AREA "B" IN WALLS OK TO COVER. ALL TRADES. MED GAS SPECIAL INSPECTOR ON SITE. 150 PSI TEST OK. PROVIDE 3RD PARTY INSPECTION & VERIFICATION DOCUMENTATION FOR FINAL APPROVAL | |
02/23/2015 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* | |
02/23/2015 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | 2 INSTALLERS COMPLETING OUTLETS | |
02/17/2015 | PLUMBING - MEDICAL GAS/TEST | Not ready for Inspection | IVRS - Inspection :* | |
02/11/2015 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* | |
02/11/2015 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | 2 INSTALLERS, MAIN RUNG (?) | |
01/27/2015 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* | |
01/27/2015 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | PRE-OP ZONE PIPING W/ 150 PSI TEST OK. SUBJECT TO SPECIAL INSPECTION. SOAP TEST ALL JOINTS. MISSING LABELS OVERHEAD. PURGE, BLOW DOWN DOCUMENTATION CHECKED ON SITE | |
01/23/2015 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* | |
01/23/2015 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | 4 INSTALLERS | |
01/22/2015 | PLUMBING - MEDICAL GAS/TEST | Not ready for Inspection | IVRS - Inspection :* | |
01/22/2015 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | JAKE NEISES W/ C-SCAN. 3RD PARTY VERIFIER. MET W/ JOE DUNN & CURTIS. RON ELMER, MARK HAMPTON W/ SUN MECH. CALL DAILY FOR PROGRESS INSPECTIONS. TYPE "L" OXY MED SPEC FOR 02, MA, & VAR. NITROGEN REGULATORS FITTINGS OK | |
01/16/2015 | PLUMBING - MEDICAL GAS/TEST | Not ready for Inspection | IVRS - Inspection :* | |
01/16/2015 | PLUMBING - MEDICAL GAS/TEST | Not ready for Inspection | NEED TO SCHEDULE MED GAS PRE CON WITH COT INSPECTOR, 3RD PARTY VERIFIER, CERTIFIED INSTALLER AND CONTRACTOR. CALL BRIAN @ 820-6738 PRIOR TO MEETING |