Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: PLUMBING - MEDICAL GAS/TEST
| Date |
Description |
Inspector |
Results |
Comments |
| 04/15/2015 |
PLUMBING - MEDICAL GAS/TEST |
|
Approved |
IVRS - Inspection :* |
| 02/25/2015 |
PLUMBING - MEDICAL GAS/TEST |
|
Partial Approval |
IVRS - Inspection :* |
| 02/25/2015 |
PLUMBING - MEDICAL GAS/TEST |
|
Partial Approval |
AREA "B" IN WALLS OK TO COVER. ALL TRADES. MED GAS SPECIAL INSPECTOR ON SITE. 150 PSI TEST OK. PROVIDE 3RD PARTY INSPECTION & VERIFICATION DOCUMENTATION FOR FINAL APPROVAL |
| 02/23/2015 |
PLUMBING - MEDICAL GAS/TEST |
|
Partial Approval |
IVRS - Inspection :* |
| 02/23/2015 |
PLUMBING - MEDICAL GAS/TEST |
|
Partial Approval |
2 INSTALLERS COMPLETING OUTLETS |
| 02/17/2015 |
PLUMBING - MEDICAL GAS/TEST |
|
Not ready for Inspection |
IVRS - Inspection :* |
| 02/11/2015 |
PLUMBING - MEDICAL GAS/TEST |
|
Partial Approval |
IVRS - Inspection :* |
| 02/11/2015 |
PLUMBING - MEDICAL GAS/TEST |
|
Partial Approval |
2 INSTALLERS, MAIN RUNG (?) |
| 01/27/2015 |
PLUMBING - MEDICAL GAS/TEST |
|
Partial Approval |
IVRS - Inspection :* |
| 01/27/2015 |
PLUMBING - MEDICAL GAS/TEST |
|
Partial Approval |
PRE-OP ZONE PIPING W/ 150 PSI TEST OK. SUBJECT TO SPECIAL INSPECTION. SOAP TEST ALL JOINTS. MISSING LABELS OVERHEAD. PURGE, BLOW DOWN DOCUMENTATION CHECKED ON SITE |
| 01/23/2015 |
PLUMBING - MEDICAL GAS/TEST |
|
Partial Approval |
IVRS - Inspection :* |
| 01/23/2015 |
PLUMBING - MEDICAL GAS/TEST |
|
Partial Approval |
4 INSTALLERS |
| 01/22/2015 |
PLUMBING - MEDICAL GAS/TEST |
|
Not ready for Inspection |
IVRS - Inspection :* |
| 01/22/2015 |
PLUMBING - MEDICAL GAS/TEST |
|
Partial Approval |
JAKE NEISES W/ C-SCAN. 3RD PARTY VERIFIER. MET W/ JOE DUNN & CURTIS. RON ELMER, MARK HAMPTON W/ SUN MECH. CALL DAILY FOR PROGRESS INSPECTIONS. TYPE "L" OXY MED SPEC FOR 02, MA, & VAR. NITROGEN REGULATORS FITTINGS OK |
| 01/16/2015 |
PLUMBING - MEDICAL GAS/TEST |
|
Not ready for Inspection |
IVRS - Inspection :* |
| 01/16/2015 |
PLUMBING - MEDICAL GAS/TEST |
|
Not ready for Inspection |
NEED TO SCHEDULE MED GAS PRE CON WITH COT INSPECTOR, 3RD PARTY VERIFIER, CERTIFIED INSTALLER AND CONTRACTOR. CALL BRIAN @ 820-6738 PRIOR TO MEETING |