Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T14CM03877
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/08/2014 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
06/25/2014 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
06/25/2014 | MECHANICAL - FINAL | Denied | PERMANENTLY ID UNITS WITH SUITE NUMBER AND A/C NUMBER. PROVIDE FRESH AIR INTAKES & BALANCE PER REQUIREMENTS FROM 2012 IMC. PAINT ALL EXPOSED PVC WITH LATEX PAINT. A/C UNIT TO THE WEST IS OVERFUSED. A/C UNIT TO THE EAST HAS A SAG IN CONDENSATE DRAIN AND IS TRAPPING WATER |