Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T14CM03855

Parcel: 11202033P


Addresses:

2000 E ROGER RD


Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T14CM03855

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/20/2015 FIRE - FINAL Approved
12/03/2014 FIRE - FINAL Denied 1. On pg A 1.0 of the approved plans the exercise room egress door # 42 has a access-controlled mag lock system this device was not indicated on the approved plans and will need to meet sections IFC 1008.1.9.8 and 1008.1.9.9
2. All doors exiting into the pool area from the lounge shall be self-closing, self -latching type only and need to meet IFC section 1008.1.9.2 exception - you can install an approved fencing before the pool and not need to change locks on doors.
3. All egress gates exiting from pool area shall meet IFC sections 1008.1.9.3 and 1008.1.9.2, gate locks cannot be double cylinder keyed dead bolt locks must be type that can be opened without the use of a key or any special knowledge or effort
4. Need two fire extinguishers 2A-10BC type one for the lounge area and other in the office area