Permit: T14CM03839

Parcel: 110120910


Addresses:

2695 N CRAYCROFT RD


Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T14CM03839

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/15/2015 FIRE - FINAL Approved
06/10/2015 FIRE - FINAL Not ready for Inspection SPOKE WITH RICK, THE GENERAL CONTRACTOR. ALARM SYSTEM INSTALLED CORRECTLY, BUT TMC MONITORING PANEL IS NOT RESETTING CORECTLY AFTER ALARMS AND TROUBLES.
06/09/2015 FIRE - FINAL Not ready for Inspection NOT READY... ALARM SYSTEM STILL NOT COMMUNICATING WITH PANEL CORRECTLY.
06/05/2015 FIRE - FINAL Not ready for Inspection NORM CALLED AND STATED THAT THE PANEL IS STILL MISCOMUNICATING WITH THE PANEL AT TMC AND THAT THEY WERE NOT YET READY FOR INSPECTION.
AS BUILDS ARE STAMPED AND ON SITE, PER NORM.
06/04/2015 FIRE - FINAL Partial Approval 1. Must submit as builds.
2. Must fix alarm issues with how the duct detectors are reporting to the proprietary monitor at TMC. Half reported as alarm and half as trouble. Should be supervisory.
3. Also, the pull station sounded a local alarm that reported to the panel on site, but was not received at TMC's panel.
What Passed -
All duct detectors were set off by smoke.
Both the Lobby Main and the IOP entrance doors auto unlocked when the pull station was pulled.
06/03/2015 FIRE - FINAL Not ready for Inspection