Permit: T14CM03752

Parcel: 121123260


Addresses:

1502 N ROSEMONT BL

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
07/21/2014 PLUMBING - GAS PRESSURE TEST Approved
07/14/2014 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
07/14/2014 PLUMBING - GAS PRESSURE TEST Not ready for Inspection CANCELLED PER MICHAEL AIR TEST NOT HOLDING
06/20/2014 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
06/20/2014 PLUMBING - GAS PRESSURE TEST Denied PROVIDE A PRESSURE TEST ON ALL NEW GAS PIPING 15 LB GAUGE
USE PRIMER & TAPE ON BLACK PIPE IN DIRT.
PROVIDE SCREWS IN ALL JOINTS OF WATER HEATER VENT CONNECTOR
SECURE GAS LINE TO WALL
REPLACE T& PVALVE AND PIPE TO OUTDOORS