Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/09/2014 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 09/05/2014 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 09/05/2014 | BUILDING - FINAL | Denied | - SELF-TAPPING SHEETMETAL SCREWS NOT APPROVED FOR GROUNDING TERMINATIONS, PER 250 NEC - TRIM OFF POINTED END OF SMS'S USED FOR LABELS ON DISC SW, MAY CAUSE DAMAGE TO CONDUCTORS - PROVIDE LADDER FOR ROOF INSPECTION - LABEL CONDUITS PER 690 NEC |