Permit: T14CM03622

Parcel: 12810079B

Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T14CM03622

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/05/2014 FIRE - FINAL Approved
08/04/2014 FIRE - FINAL Partial Approval Temp C of O OKAY for stocking and training NO PUBLIC OR SALES
1. Per approved plans need horn/strobe installed in both outside patios.
2. Need to have sound system shut down when fire alarm actives
3. All duct smokes shall be set up as supervisory signal not alarm activation.