Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T14CM03604
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/25/2014 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
06/23/2014 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
06/13/2014 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
06/13/2014 | ELECTRIC - FINAL | Denied | 1. BARE WIRING HANGING OUT OF WALL IN MECH ROOM 2. WHITE WIRE NOT TO BE USED AS HOT LEG (PANEL) 3. SMOKE ALARMS REQUIRED IN BEDROOMS AND AREA LEADING TO BEDROOMS 4. EXTENSION CORDS OR APPLIANCE CORDS NOT TO BE CONCEELED IN WALLS OR BEHIND CABINETS |