Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/01/2014 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 09/19/2014 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 09/19/2014 | BUILDING - FINAL | Denied | 1.LABELS ON SERVICE PANEL MISSING 2. PV BREAKER NOT TO PRINT 3. AC DISCONNECT TO SERVICE PANEL RACEWAY AND WIRES MISSING 4. GROUNDING ELECTRODE MISSING 5. IN THE FUTURE J BOXES TO BE ACESSIBLE WITH OUT REMOVING PANELS ON ROOF 6. PIPE RUNS TO BE 1 1/2 OFF ROOF DEEP STRUT OK NOT SHALLOW BUILDING CODE |