Permit: T14CM03541

Parcel: 117050890


Addresses:

340 N 4TH AV

Inspection Status: Approved

Inspection History: MECHANICAL - HOODS

Date Description Inspector Results Comments
09/12/2014 MECHANICAL - HOODS Approved
09/09/2014 MECHANICAL - HOODS Partial Approval DUCT PRESSURE TEST ACCEPTED BY LEERAY HANLEY
WRAP INSPECTION APPROVED BY BRUCE STEVENS
09/08/2014 MECHANICAL - HOODS Partial Approval GREASE DUCT LEAK TEST ACCEPTED AND APPROVED
09/08/2014 MECHANICAL - HOODS Denied TEST ON DUCT AND WRAP INSPECTION MUST BE WITNESSED BY INSPECTOR.
08/28/2014 MECHANICAL - HOODS Denied 1. PROVIDE 5 PSI AIR PRESSURE TEST ON DUCT
2. OPEN SIDE OF CURB FOR INSPECTION OF WRAP