Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T14CM03512
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/29/2015 | FIRE - FINAL | Approved | ||
03/25/2015 | FIRE - FINAL | Partial Approval | Temp. C of O approved Fire watch is needed and paperwork for fire watch was signed by Pastor Andy Tracy, the fire watch is for the basement only until all fire doors are installed properly. Fire watch is to be used anytime the building is occupied. For final the following shall be completed: Smoke gasket seals on all fire doors All fire doors shall be self-closing, self-latching and fire glass installed Address number posted on building (handout given) Need Hood final called in T15BU01303 |
|
03/20/2015 | FIRE - FINAL | Denied | 1. Need As builts for Ansul system to show actual layout and correct nozzles. 2. Need address numbers of 15" or more. 3. 2 Doors in fire escape route from 3rd story balcony need panic hardware. 4. Fire rated doors still need glass installed. |
|
03/12/2015 | FIRE - FINAL | Not ready for Inspection | Will need fire rated frames for entire fire rated assembly on doors 221 A and 322 ( 20 min doors). need ballards placed for gas on East side of building. Need lock box on South Wall near entrance that has access to fire alarm panel Fire extinguishers within 75 feet travel of all points in building Need fire department key box installed and a master key and FACP panel key made to be installed. |