Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/11/2014 | FIRE - FINAL | Approved | ||
| 07/10/2014 | FIRE - FINAL | Partial Approval | Final Approval subject to the building official approval to the corridors fire rating. | |
| 07/03/2014 | FIRE - FINAL | Denied | Per IBC and IFC 1018.1 Occupant load great than 30 all corridors shall be 1 hour fire resistance rated and all doors into corridor shall be 20 min rated Need 2 2A-10BC fire extinguishers mounted on wall Per IBC & IFC sec. 1030 exit signs shall be battery back, when tested exit failed to work need to repair or replace. |