Permit: T14CM03406

Parcel: 12511055A


Addresses:

1001 N ALVERNON WY

Inspection Status: Approved

Inspection History: FIRE - FINAL

Date Description Inspector Results Comments
11/17/2014 FIRE - FINAL Approved
11/03/2014 FIRE - FINAL Denied 1. All duct smokes shall be installed on the fire alarm system as supervisory signal
2. Shall repair FDC someone removed the threads on one side.
3. Need annual fire alarm inspection
4. Need annual fire sprinkler inspection
5. Need 5 year check valve inspection
6. Need lock out install on breakers for the fire bell and the fire alarm system - NOTE make sure the fire alarm system is on a dedicated circuit.
7. Need 12" inch address number posted on building, handout given.