Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/26/2014 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 08/25/2014 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* | |
| 08/22/2014 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 08/15/2014 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* | |
| 08/15/2014 | MECHANICAL - FINAL | Partial Approval | SOME FITTINGS ON VENT CONNECTORS ARE UPSIDE DOWN PROVIDE 6" CLEARANCE FROM ARMAFLEX AT VENT CONNECTOR SOUTH UNIT | |
| 07/18/2014 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 07/18/2014 | MECHANICAL - FINAL | Denied | AT BOTH COMMON VENT CONNECTORS; REPLACE DAMAGED TEE FITTINGS. INSTALL A FACTORY, LISTED TEE WITHOUT MODIFICATIONS | |
| 06/30/2014 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 06/30/2014 | MECHANICAL - FINAL | Denied | ON SOUTH SIDE CONDENSATE TRAP IN FURNACE NOT GLUED. DOUBLE WALL VENT NOT ALLOWED TO CONVERT TO SINGLE WALL. YOU CAN USE A DOUBLE WALL TEE IF NECESSARY. PROVIDE SCREWS IN ALL JOINTS OF VENT CONNECTORS & RE SCREW WATER HEATER VENTS WHERE SCREWS ARE MISSING | |
| 06/11/2014 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* |