Inspection History Details
Inspection Status: Denied
Inspection History: FIRE SPKLR - FINAL
Permit Number - T14CM03329
Inspection Description - FIRE SPKLR - FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/27/2015 | FIRE SPKLR - FINAL | Denied | 1.Have no documentation of alarm system testing. 2.Have no documentation of sprinkler system working at building... 3.sprinkler permit was not called in. Last inspector required contractor to call in permit. need to: 1.do shut down of AC to see back up exit sign lighting and emregency lighting. 2.see alarm panel locked out. 3.see documentation that alarm system is monitored. 4.escutcheon plate in main lobby hallway 5.hole in training room ceiling near sprinkler head 6.storage room ( HR) head too far from the East wall ( does not qualify for small room rule) 7.Eliminate ( right hand arrow) on exit sign in HR hallway to East Exit 8.Remove additional lock on SE exit HR hallway 9.Visitors storage area - head too far off wall ( this is storage so the small room rule does not apply). 10.Patch holes in jaintors ceiling near sprinkler head 11.Missing escutcheon plate on BUndles call store Floor near OM conference room 12.fire extinguishers placed within 75 feet walking distance of Every place in building |
|
09/09/2014 | FIRE SPKLR - FINAL | Denied | 1. Please have sprinkler contractor call in their permit |