Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/28/2014 | FIRE - FINAL | Approved | ||
| 11/21/2014 | FIRE - FINAL | Partial Approval | 1. Need to check on status of Underground piping of new fire hydrant. | |
| 11/03/2014 | FIRE - FINAL | Denied | Need fire hydrant (1500 GPM) within 400 feet of structure on the approved plans show 450 feet as the bird fly's but on site over 800 feet. Need hydrant located within 400 feet as a fire truck drives to lay hose to the structure. Note: Will need a permit before work can be done |