Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T14CM03195
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/22/2016 | FIRE - FINAL | Approved | ||
04/14/2016 | FIRE - FINAL | Partial Approval | ok to occupy new area, still need to address emergency egress lighting,exiting issues brought up during inspection and fire sprinklers that are obstructed with foil. | |
08/26/2015 | FIRE - FINAL | Partial Approval | Inspected pharmacy area only - 14 heads will be on static pressure so Wal-Mart can open the pharmacy by midnight tonight (see marked plans). STILL NEED TO DO A HYDRO PRESSURE TEST AT 200 PSI FOR 2 HOURS Test one horn/strobe in pharmacy and one strobe I bathroom for pharmacy |
|
08/25/2015 | FIRE - FINAL | Partial Approval | FOR PHARMACY ONLY - 1. MISSING SPRINKLER HEADS ( 4 PENDANT) ON PLANS FOR OVER THE CUSTOMER COUNTER ( WALMART STORE SIDE). EXISTING SPRINKLERS ARE TOO FAR OFF WALLS BECAUSE OF NEW PHARMACY WALL BEING BUILT. 2.SPRINKLER INSTALLATION COMPANY DID NOT CALL IN THEIR INSPECTION. 3.FIRE ALARM PERMIT NEEDED FOR INSTALLATION OF STROBE IN PHARMACY. ALARM PERMIT IS REQUIRED ON APPROVED PLANS ON FIRE APPROVALS STAMP. 4.ONE BULB IN EMERGENCY LIGHTS ON WALL IS NOT WORKING. WALMART WANTS TO OCCUPY THE PHARMACY IN A FEW DAYS. MUST PASS SPRINKLER AND ALARM FINALS AND REPLACE A BULB IN THE EMERGENCY LIGHT IN PHARMACY BEFORE THEY MAY OCCUPY. |