Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T14CM03186
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/21/2014 | FIRE - FINAL | Approved | ||
10/20/2014 | FIRE - FINAL | Denied | 1. Fire alarm final to keep sounding it kept cutting out in the middle of the message one strobe in the back storage room failed to sound or flash. 2. Using NFPA 13 table 8.6.5.1.2 2010ed heads blocked by soffit on sales floor in boys department spray pattern cannot get to wall. 3. No heads in fitting rooms 4. Front window display head blocked by rack system cover plate cannot fall off and spray pattern is blocked. 5. Front display and main entrance cover plates on sprinkler heads are mudded in place cover plate will not fall off when needed clean plates or replace. |