Permit: T14CM03186

Parcel: 10511061R

Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T14CM03186

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/21/2014 FIRE - FINAL Approved
10/20/2014 FIRE - FINAL Denied 1. Fire alarm final to keep sounding it kept cutting out in the middle of the message one strobe in the back storage room failed to sound or flash.
2. Using NFPA 13 table 8.6.5.1.2 2010ed heads blocked by soffit on sales floor in boys department spray pattern cannot get to wall.
3. No heads in fitting rooms
4. Front window display head blocked by rack system cover plate cannot fall off and spray pattern is blocked.
5. Front display and main entrance cover plates on sprinkler heads are mudded in place cover plate will not fall off when needed clean plates or replace.