Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T14CM03112

Parcel: 118033850


Addresses:

2430 S FICKETT AV


Inspection Status: Denied

Inspection History: ELECTRIC - RECONNECT

Permit Number - T14CM03112

Inspection Description - ELECTRIC - RECONNECT

Inspection Status - Denied

Date Description Inspector Results Comments
06/05/2014 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
06/05/2014 ELECTRIC - RECONNECT Approved
05/27/2014 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
05/23/2014 ELECTRIC - RECONNECT Not ready for Inspection INSPECTION NOTES TRANSFERED FROM CLOSED PERMIT T09EL01533

IVRS - Inspection :
See detailed listing on site.| 999*
1) SERVICE EQUIPMENT TO BE LABELED BY ADDRESS AND UNIT NUMBERS (METAL LABELS)
2) NEED 12'-0" CLEARNACE, OVERHEAD CONDUCTORS TO GROUND
3) SERVICE TO BE GROUNDED AT METER TWO GROUND RODS, ONE AT SUB-PANEL
4) NEED GROUND TERMINAL INSTALLED AT SUB PANEL
5) NEED TO HAVE A MAX BREAKER OF 60 AMPS AT SUB PANEL
6) PLEASE OPEN SUB-PANEL INSIDE HOUSE
7) LABEL ALL CIRCUITS