Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/15/2014 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 07/31/2014 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 07/31/2014 | BUILDING - FINAL | Denied | 1. GROUND RODS ONLY 2' APART- AS PER LAST INSPECTION, CONVERSATION WITH SOLAR CITY PERSON ON SITE AND NEC GROUNDS MUST BE 6' APART MIN RE-INSPECTION FEE NEXT INSPECTION 2. DEAD FRONT NOT ACCEPTABLE |
|
| 07/25/2014 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 07/25/2014 | BUILDING - FINAL | Denied | - GROUNDING ELECTRODES 2-RODS 6' APART - EXISTING ROD NEEDS TO BE FLUSH WITH GRADE - A RE-INSPECTION FEE IS ASSESSED AS PER LAST INSPECTION. PAY RE-FEE PRIOR TO NEXT INSPECTION |
|
| 07/22/2014 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 07/22/2014 | BUILDING - FINAL | Not ready for Inspection | RE-INSPECTION FEE NEXT INSPECTION IF NOT COMPLETE | |
| 06/23/2014 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 06/23/2014 | BUILDING - FINAL | Denied | LOOSE FITTINGS ON ROOF PANEL MISSING DEAD FRONT LABEL NEUTRAL NOT TERMINATED PER CODE IN SERVICE PANEL EXPOSE GROUNDING ELECTRODE SYSTEM |