Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/24/2014 | BUILDING - FINAL | Approved | ||
| 09/16/2014 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 09/16/2014 | BUILDING - FINAL | Denied | 1. COMPLETE GROUNDING ELECTRODE SYSTEM GROUNDING TO GROUNDING ELECTROD. WIRE COILED UP UNDER PANEL?? 2. LABELS TO BE RIVITED OR SCREWED TO ENCLOSURES |
|
| 07/22/2014 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 07/22/2014 | BUILDING - FINAL | Not ready for Inspection | COMPLETE GROUNDING, PROVIDE PLANS/PER,ITS A-REINSPECTION FEE WILL BE ASSESED NEXT INSPECTION IF NOT COMPLETE AND PLANS/PERMITS NOT ON SITE |