Permit: T14CM03005

Parcel: 126133650


Addresses:

4526 E 18TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/17/2014 ELECTRIC - FINAL Approved IVRS - Inspection :*
06/11/2014 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
06/11/2014 ELECTRIC - FINAL Denied 4528:
- EQUIP GROUND SHOULD BE #10 AWG PER 250-122 NEC
- SHEET METAL SCREW NOT APPROVED FOR GROUND TERM IN J-BOX 250 NEC
4526:
- EQUIP GROUND SHOULD BE #10 AWG PER 250-122 NEC
- VERIFY GAS & WATER BOND
- SHEET METAL SCREW NOT APPROVED FOR GROUND TERM IN J-BOX - 250 NEC