Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/17/2014 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/11/2014 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 06/11/2014 | ELECTRIC - FINAL | Denied | 4528: - EQUIP GROUND SHOULD BE #10 AWG PER 250-122 NEC - SHEET METAL SCREW NOT APPROVED FOR GROUND TERM IN J-BOX 250 NEC 4526: - EQUIP GROUND SHOULD BE #10 AWG PER 250-122 NEC - VERIFY GAS & WATER BOND - SHEET METAL SCREW NOT APPROVED FOR GROUND TERM IN J-BOX - 250 NEC |