Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/08/2014 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 09/29/2014 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 09/29/2014 | ELECTRIC - SERVICE UPGRADE | Denied | 1.WIRES AL# 2/0 IN RISER TO BE 4/0 AL FOR 200AMPS 3/0.15 B.7 2.GROUND RODS TO BE BELOW GROUND LEVEL/250.53G 3.GAS BOND MISSING |