Date Description Inspector Results Comments
10/08/2014 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
09/29/2014 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
09/29/2014 ELECTRIC - SERVICE UPGRADE Denied 1.WIRES AL# 2/0 IN RISER TO BE 4/0 AL FOR 200AMPS 3/0.15 B.7
2.GROUND RODS TO BE BELOW GROUND LEVEL/250.53G