Permit: T14CM02822

Parcel: 114475960

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T14CM02822

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/08/2015 BUILDING - FINAL Approved IVRS - Inspection :*
05/04/2015 BUILDING - FINAL Partial Approval IVRS - Inspection :*
05/04/2015 BUILDING - FINAL Partial Approval CONT "NR" INSPECTIONS MAY RESULT IN RE-FEES. COMPLETE NOTED CORRECTIONS. PROVIDE OVERFLOW SENSOR. UV PROTECTION LOCKING CAPS. PIPE DRAIN PAN OFF OF PLATFORM
04/23/2015 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*
04/23/2015 BUILDING - FINAL Not ready for Inspection PROVIDE CERTIFICATE OF ENERGY STAR COMPLIANCE. (N11.2.4.1.2) IRC PG 484. COMPLETE WORK AND ALL NOTED CORRECTIONS. AN AVB MAY NOT HAVE VALVES DOWN; IRC T P2902.3. PROVIDE CODE COMPLIANT BACKFLOW PROTECTION FOR IRR SUPPLY. WATER HAMMER ARRESTERS REQUIRED. PROVIDE A WATER HEATER DRAIN PAN. PROVIDE ARC SHIELDS ON OUTLETS MORE THAN 1/4" BACK AT COMBUSTIBLES. SECURE OUTLETS. ALL GARAGE OUTLET RECEPTACLES SHALL BE GFI PROTECTED. REMOVE OR SECURE RECEPTACLE AT MAIN PANEL. LABEL PANEL "NON-METALLIC WATER TUBING, NO BOND." PROVIDE A LOCKOUT ON WH CIRCUIT. CO PLUGS SHALL BE LISTED TO RECEIVE SCREW AND SHALL BE ACCESSIBLE. APPLIANCES IN GARAGE REQUIRED TO BE ELEVATED 18" ABOVE FLOOR PER M1307.3. INSPECTION STOPPED (TOO MANY ITEMS).
04/20/2015 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*
04/20/2015 BUILDING - FINAL Not ready for Inspection CANCELED BY DAVE
04/17/2015 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*
04/17/2015 BUILDING - FINAL Not ready for Inspection NOT READY FOR FINAL INSPECTION. PARTIAL LIST ONLY. PLANS AND PAPERWORK REQUIRE REVISION. SECURE CLOSET FLANGES TO FLOOR. PROVIDE A G AT SOFTENER DRAIN. DRYER EXHAUST LENGTH SIGN. INSTALL AND SEAL ALL CLEANOUT FITTINGS AND PLUGS. GAS REGULATOR VENT IS REQUIRED TO TURN DOWN TO PREVENT THE ENTRY OF WATER G2421.3 (OK IF SW GAS INSTALLED) IRRIGATION SUPPLY REQUIRES A PRESSURE VACUUM BREAKER WITH TEST REPORT. INSPECTION STOPPED. COMPLETE WORK
01/29/2015 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*
01/29/2015 BUILDING - FINAL Not ready for Inspection REVISION FOR ELECTRICAL CHANGE REQ PRIOR TO BUILDING FINAL
09/08/2014 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*
09/04/2014 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*
09/04/2014 BUILDING - FINAL Not ready for Inspection #1412
08/29/2014 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*
08/29/2014 BUILDING - FINAL Not ready for Inspection RED LINE CHANGES ON PLAN