Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/06/2014 | ELECTRIC - FINAL | Approved | 12" - 18" BURIAL DEPTH IS EXISTING UNDER PAVEMENT. NO NEW FEEDERS ADDED FROM THIS 20 - 30 YEAR OLD INSTALLATION. 30A CIRCUIT PROTECTION OK. NEW SUB-SERVICE OK | |
| 06/04/2014 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 06/04/2014 | ELECTRIC - FINAL | Denied | - CONDUIT FEEDING METER BASE/RECEPTACLE UNDER TREE TOO SHALLOW, CODE DEPTH PER 300.5 NEC = 24" TO FINISHED GRADE. NEED TO VERIFY ENTIRE RUN. PROVIDE APPROVED PLANS WITH FEEDER LOCATION & TERMINATION LOCATION, INCLUDE ALL INFORMATION REQUIRED FOR PLAN SUBMITTAL |