Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T14CM02636
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/01/2014 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
06/17/2014 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
06/12/2014 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
06/12/2014 | PLUMBING - INTERMEDIATE | Denied | PROVIDE VERTICAL VENTS AS SHOWN & REQ BY CODE. 3 COMP SINK SHALL BE ALL INDIRECT PER CODE. WC NOT VENTED. TRANSITION GLUE MAY NOT BE USED IN BUILDING. REMOVE ABANDONED DEAD LEGS OF VENT |